sti-usa - Indexsti-usa - STI General Catalog - IndexSTI STOPPER ® II HEATED ENCLOSURE
DESCRIPTION
The Stopper II is a patented device that has been helping stop false fire alarms
around the world for more than 25 years, without restricting legitimate alarms.
This Stopper II Heated Enclosure allows addressable dual monitor modules to
be installed inside or outside in temperatures below UL Listing limits or in
other NEMA 3R environments. UL/cUL Listing requires use of an outdoor rated
station (the station has sealed contacts). The cover offers excellent protection
against physical damage (both accidental and intentional), as well as other
environments inside and outside. Also ideal for inside of walk-in freezers.
Specifications
Internal Dimensions:
PART # HEIGHT WIDTH DEPTH
1200A-HTR
1200A-HTR240
6.25 in.
(158mm)
4.125 in.
(104mm)
1.25 in.
(31mm)
Polycarbonate Enclosure:
Flammability: UL94 V-2
Wall Thickness: backbox: .20 inches (5.1mm)
cover: .12 inches (3.1mm)
NEMA Rating: 3R
Warranty: Lifetime against breakage in
normal use (one year on electronics
from time of installation)
Silicone Laminate Heater:
STI-1200A-HTR 110 VAC 50/60 Hz UL Recognized Component
STI-1200-A-HTR240 240 VAC 50/60 Hz UL Recognized Component
100 Watts
Life: @ -10˚C (14˚F) ~ 70˚C (158˚F) 5 years
Duty Cycle: -40˚F (-40˚C) 16%
-70˚F (-57˚C) 38%
Fan:
-99˚F (-73˚C) 100%
24 VDC (±10%), 90 mA UL Recognized Component
Life: 5 years continuous duty
! WARNING: The polarity of the circulating fan is important
as it only rotates in one direction with red lead being positive.
Gasket:
Material: Neoprene
Life: 5 Years
FEATURES
• For use in areas where temperature or
environmental conditions exceed the operating
range of addressable manual pull stations.
• Fan runs continuously to maintain a uniform
temperature inside the enclosure.
• Heater unit cycles as required to maintain the
correct range of operating temperature.
• Enclosure rated to NEMA 3R Standards, ADA
Compliant for operation (equivalent to an IP 44
Rating).
• Meets ADA operational requirements.
UP
4
5
3
1
2
Temp
DEG C
50
40
30
20
10
0
-10
-20
-30
-40
-50
-60
-70
-80
00:00
00:30
01:00
01:30
STI-1200A-HTR
STI-1200A-HTR
TC-1 TC-2 TC-3 TC-4 TC-5 External Temp
• UL Listed to U.S. and Canadian safety standards for
dual monitor addressable modules using a standard
outdoor listed station down to -70°F (-57°C) UL File
S2466 and S7255 (non-fire).
• Polycarbonate backed by a lifetime guarantee
against breakage in normal use (one year on
electronics).
• UL Listing does not require standby or secondary
power for the 110 or 240 VAC 50/60 Hz heater.
• The thick, clear polycarbonate cover is UV-stabilized
which helps against discoloration.
02:00
02:30
ELAPSED TIME (hours: minutes) TC = Thermocouple
NOTE: UL Listing requires low temperature thermostat to be monitored by a