sti-usa - Index

sti-usa - STI General Catalog - Index

Dimensions and Technical Information
STI-1229HTR, STI-1229HTR-HAZ Specifications
NOT PROVIDED
IN AREAS WHERE FREQUENT
WASH DOWNS OCCUR
WASHERS MAY BE USED TO
STAND OFF ENCLOSED SPACER
1/4 in. (6.3mm)
DIA. HOLE
FEATURES
!
Testing
Approvals
LOW VOLTAGE
ELECTRICAL ENTRY
ANCHOR
(4) PROVIDED
SCREW #10 x 1 1/2 in.
(4) PROVIDED
STANDOFF
LOW VOLTAGE TERMINAL BLOCK
3/4 in. CONDUIT HUB
3/4 in. NPT NIPPLE
(NOT PROVIDED)
HIGH VOLTAGE
ELECTRICAL ENTRY
SEALING HUB
(NOT PROVIDED)
3/4 in. NPT NIPPLE
(NOT PROVIDED)
ENCLOSED SPACER
LOW TEMP
WARNING
THERMOSTAT
WARNING LABEL
SEALING HUB
(NOT PROVIDED)
Polycarbonate Enclosure UL-50:
Flammability: UL94V-2
Wall Thickness: 0.2 in (5.1mm)
NEMA Rating: 4X, indoor and outdoor use
Hazardous Rating: Class II Groups F&G Div. 2
and Class III locations
Warranty: Lifetime against breakage in normal use.
Polycarbonate Backbox:
Wall Thickness: 0.2 in (5.1mm)
Bottom Thickness: 0.125 in (3.175mm)
Silicone Laminate Heater:
110/240 VAC 50/60 Hz UL Recognized Component
100 Watts
Life: @ -10˚C (14˚F) ~ 70˚C (158˚F) 5 Years
Duty Cycle: -40˚F (-40˚C) 53%
-70˚F (-57˚C) 71%
Fan:
24 VDC, 90 mA UL Recognized Component
Life: 5 Years Continuous Duty
WARNING: The polarity of the circulating fan is important as
it only rotates in one direction with red lead being positive.
Gasket:
Material: Neoprene
Life: 5 Years
It has been tested and approved or listed by:
• UL and cUL, NEMA 4X, and UL 50 File S7025
• UL Hazardous File E228169 NEMA 4X
• In Canada, ULC Listed strobes are required for hazardous
locations; cUL is acceptable for non-hazardous
• Equivalent to an IP 66 Rating
HEATER ASSEMBLY
FAN
HIGH VOLTAGE TERMINAL BLOCK
STANDOFF
APPLIANCE MOUNTING PLATE
FUSE
Warnings
CONTROL THERMOSTAT
SCREW #8-32 x 3/8 in. (4) PROVIDED
EXISTING STROBE APPLIANCE
GASKET (1) PROVIDED
SOLID CLEAR COVER
PRODUCT DIMENSIONS
9.37 in.(238mm)
2.87 in.(73mm)
APPLIANCE MOUNTING
BACKPLATE
7.25 in.(184mm)
WASHER (6) PROVIDED
#8-32 x 3/4 in. SOCKET
CAP SCREW (6) PROVIDED
5.5 in.
(140mm)
The enclosure is used to protect UL Listed 1638 and 1971 visual
notification appliances at temperatures down to -70˚F (-57˚C). It is
the installer’s responsibility to comply with NEC70 Articles 502 and
503, NFPA72 and other applicable fire and electrical codes. Conduit or
raceway paths need to be sealed as near to the enclosure as possible.
Installer should have maintained supervision over the low
temperature thermostat. The low temperature monitoring thermostat
makes the circuit at 32°F (0°C) and clears the circuit at +50°F (+10°C).
This listing requires that the fire alarm supervisory control module be
only of the latching type. The heater assembly and gasket have a life
of five years. After such date a replacement heater assembly can be
purchased (STI-HK2A). On the heater assembly is a label where you
should record the installation date.
! WARNING: In hazardous areas all sources of power must be
shutdown before accessing cover per NEC.
Performance Review for STI-1229HTR
Manufacturer
WHEELOCK (RSS 24MCW)
ADT SECURITY (ADTG1-V SERIES), EST/EDWARDS (G1-V SERIES, G1-HV
SERIES, G1-HOV SERIES, EG1-V SERIES, EG1-HV SERIES, EG1-HOV SERIES),
HONEYWELL (XLSG1-V SERIES, XLS1-HV SERIES), MIRCOM (MG1-V SERIES,
MG1-HV SERIES, MG1-HOV SERIES), MIRTONE (MG1-V SERIES), SIEMENS
(G1-V SERIES)
FARADAY LLC (2700)
EST/EDWARDS (2440S SERIES, 202 SERIES), HONEYWELL (XLS202 SERIES),
MIRCOM (MS SERIES), SIEMENS (202 SERIES), ZITON PTY LTD (ZG1-V-SERIES)
Light
Loss %
31%
32%
33%
34%
AMSECO (SL24W-153075), AMSECO COLORED LENSES (SLW24-153075 A, B,
G OR R, SL24C-3075110 A, B, G OR R, CSL24W- A, B, G OR R, CSL24C - A,
B, G OR R), HONEYWELL (XLSG1-HOV SERIES), MIRCOM (FS-240), POTTER
ELECTRIC (AS-24-153075R, AS-24-153075W)
37%
Performance Review for STI-1229HTR-HAZ
FARADAY LLC (2700) 33%
SYSTEM SENSOR (SS24110ADA) 35%
AMSECO (SL24W-153075), GENTEX (GES24-15/75 W, R OR P) 36%
19